Leave Your Message

China Non-woven Fabric Film Wrapped Flat Wire - Quality Suppliers & Factory for Electrical Applications

Non-woven Fabric Film Wrapped Flat Wire, produced through an advanced extrusion process, features flat copper (or aluminum) wire enveloped in 2-3 layers of high-quality polyester film and electrical non-woven fabric insulation. This design ensures exceptional voltage resistance, making it highly suitable for the manufacturing of various types of reactors, As a leading manufacturer and supplier based in China, Hengte Electric Power is committed to delivering top-notch Non-woven Fabric Film Wrapped Flat Wire. Our state-of-the-art factory is equipped with cutting-edge production lines and precision testing instruments, coupled with a robust research and development team. We prioritize strict quality control to maintain high standards throughout the manufacturing process. For inquiries about our magnet wire products, please reach out to us, and our team will respond promptly

    Product Information

    Product model: WM(L) (B)-0.20~1.25

    This product is produced by extrusion process (flat) copper (aluminum) wire wrapped with 2–3 layers of polyester film and electrical non-woven fabric as insulation layer, with excellent voltage resistance.

    ⚡ Suitable for manufacturing type reactors.
    Production Range
    ① Cloth Covered Copper / Aluminum Flat Wire

    Thickness size — A: 0.80 ~ 5.60 mm

    Thickness size — B: 2.00 ~ 16.00 mm

    ② Cloth Covered Copper / Aluminum Round Wire

    Diameter — D: 1.90 ~ 5.00 mm

    📞 If you require specifications beyond the above range, please contact us.
    Conductor Material
    • Al
      The aluminum wire meets the requirements of GB/T 55843-2009. Resistivity at 20°C: ≤ 0.02801 Ω·mm²/m.
    • Cu
      The copper wire complies with the requirements of GB/T 55842-2009. Resistivity at 20°C: ≤ 0.01724 Ω·mm²/m.
    Technical Parameters
    Dimensions of Circular Conductors
    Nominal Diameter Deviation
    0.90 < d ≤ 2.50 +0.013
    2.50 < d ≤ 3.00 +0.025
    3.00 < d ≤ 5.00 +1%d
    Elongation of Circular Conductors
    Nominal Diameter Minimum Elongation (%)
    0.90 < d ≤ 2.50 15
    2.50 < d ≤ 5.00 20
    Frequently Asked Questions
    Q What is the product model of this cloth-covered wire?
    The product model is WM(L) (B)-0.20~1.25. It is produced by an extrusion process using flat copper or aluminum wire wrapped with 2–3 layers of polyester film and electrical non-woven fabric as the insulation layer.
    Q What applications is this wire suitable for?
    This wire is designed for manufacturing type reactors. Its multi-layer insulation construction provides excellent voltage resistance, making it ideal for demanding electromagnetic applications.
    Q What size ranges are available for the flat wire and round wire?
    For flat wire, thickness size A ranges from 0.80–5.60 mm and size B from 2.00–16.00 mm. For round wire, the diameter D ranges from 1.90–5.00 mm. Custom sizes outside these ranges are available upon request.
    Q What are the resistivity requirements for the copper and aluminum conductors?
    The aluminum wire must have a resistivity ≤ 0.02801 Ω·mm²/m at 20°C (per GB/T 55843-2009), while the copper wire must have a resistivity ≤ 0.01724 Ω·mm²/m at 20°C (per GB/T 55842-2009).
    Q What are the dimensional tolerances for circular conductors?
    Dimensional deviation varies by diameter: for 0.90 < d ≤ 2.50 mm it is +0.013; for 2.50 < d ≤ 3.00 mm it is +0.025; and for 3.00 < d ≤ 5.00 mm it is +1%d.
    Q What is the minimum elongation requirement for circular conductors?
    For circular conductors with a nominal diameter of 0.90 < d ≤ 2.50 mm, the minimum elongation is 15%. For conductors with a diameter of 2.50 < d ≤ 5.00 mm, the minimum elongation is 20%.